This removable DC input connector block is for the Version 1 930 W -48 VDC power supply (UCSC-PSU-930WDC) used in Cisco UCS C-Series rack servers. It suits telco, central-office and NEBS-environment installations where servers run from a -48 VDC facility feed, and it is also the part to order when a connector block is lost or damaged.

The block has three spring-cage wire terminals for ground, DC negative and DC positive. Wires are field-terminated with a 15 mm (0.59 in) strip length, using 8 AWG wire recommended and 10 AWG as the minimum gauge. Terminate the wires in order from lower to upper: green (ground), black (DC negative), then red (DC positive). An orange push button on top releases the block from the power supply.

The host power supply accepts a nominal -48 to -60 VDC input, draws up to 23 A at -48 VDC and delivers up to 930 W at 12 VDC. This connector is for the Version 1 supply only. The Version 2 supply, UCSC-PSU2V2-930DC, uses a fixed 3-wire block and does not use this part.

Enquire with XS Network Tech for new or used pricing and availability.

Features

- Spring-cage terminals clamp bare DC wires, released with a small screwdriver on the wire retainer levers
- Removable block lets DC wiring be prepared or replaced without replacing the power supply
- Orange push-button release for the connector block
- Polarity aligns with the '+ DC' label on the power supply when reinserted
- Supports telco and NEBS-style -48 VDC deployments on UCS C-Series servers

Warranty

All products sold by XS Network Tech include a 12-month warranty on both new and used items. Our in-house technical team thoroughly tests used hardware prior to sale to ensure enterprise-grade reliability.

All technical data should be verified on the manufacturer data sheets.

View full details

specs-tabs

Collapsible content

Technical Specifications

FAQs

Technical Specifications

- Spare part number: UCSC-CONN-930WDC=
- Product type: Removable DC input connector block
- Used with: 930 W DC (Version 1) Power Supply, UCSC-PSU-930WDC
- Not used with: Version 2 930 W DC Power Supply, UCSC-PSU2V2-930DC
- Terminals: 3 spring-cage wire connectors
- Termination order (lower to upper): Green (ground), Black (DC negative), Red (DC positive)
- Wire strip length: 15 mm (0.59 in)
- Recommended wire gauge: 8 AWG
- Minimum wire gauge: 10 AWG
- Release: Orange plastic push button on top of the connector
- Host PSU input voltage: Nominal -48 to -60 VDC (range -40 to -60 VDC)
- Host PSU maximum input current: 23 A at -48 VDC
- Host PSU maximum input power: 1104 W
- Host PSU maximum output power: 930 W
- Host PSU output voltage: 12 VDC
- Host PSU form factor: RSP1 (C-Series 2U and 4U servers)

FAQs

Q: Which power supply does this connector block fit?
A: It fits the Version 1 930 W DC power supply, UCSC-PSU-930WDC, used in UCS C-Series 2U and 4U (RSP1) rack servers such as the C240 M4, C220 M4 and HX240c M4.

Q: Can I use it with the Version 2 930 W DC power supply?
A: No. The Version 2 supply, UCSC-PSU2V2-930DC, has a fixed 3-wire block with a supplied connector cable and does not use this removable connector.

Q: What wire do I need to terminate into it?
A: Strip the wire back 15 mm (0.59 in). Cisco recommends 8 AWG, with 10 AWG as the minimum gauge.

Q: In what order are the wires connected?
A: From lower to upper, connect green (ground), black (DC negative) and red (DC positive). Turn off DC power at the facility circuit breaker before wiring.

Q: How do I remove the connector block from the power supply?
A: Push the orange plastic button on top of the connector toward the power supply, then pull the block out.

Recently Viewed

  • Request a Quote

    Looking for competitive pricing? Submit a request, and our team will provide a tailored quote that fits your needs.

  • Contact Us Directly

    Have a question or need immediate assistance? Call us for expert advice and real-time support.

    Call us Now  
  • Contact Us Directly

    Have a question or need immediate assistance? Call us for expert advice and real-time support.

    Contact us